What are the aspects of maintenance and use of diesel generators
Browse: Release Date: 2019-11-18
What are the aspects of maintenance and use of diesel generators
Diesel generating units are generally used in emergency situations in various power units. The daily maintenance of diesel generating units is directly related to whether they can really play an emergency role at critical moments, so users must do their daily maintenance. Operation, so that the diesel generator set is always in a good standby state and prolong the service life. The daily maintenance of diesel generator rental generally includes the following aspects:
a What are the aspects of maintenance and use of diesel generators
1. When the diesel generator set is in the standby state, the voltage, level of the liquid, the specific gravity of the electrolyte and the usage of the battery pile head should be checked frequently. When the voltage of the starter battery is found to be low, the starter battery should be charged in time. Charging should be performed strictly in accordance with the battery manufacturer's instruction manual to prevent damage to start the battery diesel generator rental.
When it is found that the electrolyte level of the electrolyte is lower than the standard, it should be replenished in time. Only distilled water or battery replenishment must be added when replenishing. Dilute sulfuric acid must not be added, otherwise the proportion of the electrolyte will become higher and higher, causing battery damage .
A generator set with a computer control screen and a unit using an automatic charger should keep the charger on at all times to prevent the battery from losing power due to the long-term use of power by the computer control screen. If you do not use a computer control screen and use a manual charger, the startup battery should be charged every half a month if the startup battery is faultless.
2. Stand-by diesel generators should be tested at no load every half a month. However, during no-load test, the actual time should not exceed 15 minutes each time, especially when the engine cooling water temperature is low. Too long, so as not to cause diesel engine rental due to the incomplete combustion of fuel due to the low temperature of the engine.